Project Summary
Our client needed a current arc flash hazard assessment for a large paper mill to support NFPA 70E electrical safety compliance. We carried out an extensive field verification of the 480V distribution system, covering 196 electrical rooms and 469 MCC lineups. The survey documented 550 variable frequency drives, 2,303 feeder breakers, and 2,278 motor starters (1,115 size 1, 446 size 2, 291 size 3, 216 size 4, 193 size 5, and 17 size 6). We captured more than 15,000 field photographs, including over 11,000 MCC bucket images and nearly 4,000 motor equipment photos, and used this data to build a new electrical system model of the facility.
We then completed the study. We reviewed and reconciled several legacy models from earlier projects against the new master model, and performed targeted field verification wherever discrepancies appeared. This gave Our client a single validated model to serve as the authoritative reference for future engineering studies, system modifications, and electrical safety programs. Using that model, we reviewed the short circuit and arc flash results for equipment exceeding available interrupting ratings, elevated incident energy levels, and equipment needing updated labeling. We documented the findings in an exceptions report that identified issues and areas of concern without corrective-action recommendations. We also printed and installed approximately 3,500 updated arc flash warning labels, with quantities based on the number of buses in the model, so electrical workers are informed of the hazards when working on energized equipment.
Deliverables
- Consolidated electrical system model
- Arc Flash and Short Circuit Exceptions Report
- Updated arc flash calculation results
- Installation of approximately 3,500 arc flash warning labels throughout the facility
Services Provided
- Field verification of 480V electrical distribution equipment
- Electrical model consolidation and verification
- Targeted field verification of model discrepancies
- Short circuit and arc flash analysis review
- Exceptions reporting
- Arc flash label printing and installation